Gas detection system
Gas system controllers
GC-06
A large number of different digital detectors from the MSR series can be connected to GC-type control units: PollyGard 2 and PolyXeta 2, as well as four analog detectors, and PDP-13EX detectors suitable for detecting explosive gases in boiler rooms and siProduct Description
The GC-06 microprocessor-based gas detection control panel consists of a basic module that enables the connection of digital detectors, with the option to connect up to four analog detectors. Due to its functional characteristics and compact design, the GC-06 is particularly suitable for small and medium-sized gas detection systems.
The GC-06 model also serves as a replacement solution for existing AUSY-type systems, which will soon be discontinued. It is important to emphasize that support for AUSY systems will not be discontinued — spare parts, service, and technical support for existing installations will continue to be available.
The GC-06 control panel is compatible with our best-selling PDP-13 EX detectors, with more than 20,000 units already installed on the market. This allows for easy modernization and replacement of older systems without requiring major interventions on the existing installation, ensuring continuous operation and long-term system reliability.
The control panel is designed in accordance with relevant international standards and directives, ensuring its applicability across various fields — from building management and industrial facilities to maritime applications. Its construction and functionality meet the strict safety requirements of SIL2 (Safety Integrity Level 2) according to EN 61508, confirming a high level of reliability and operational safety.
GC-06-000, GAS DETECTION CONTROL PANEL
Power supply: 230/110 V AC <> 24 V DC, 2×2 Ah integrated batteries
LCD display showing detector status with audible and visual LED indicators
Four programmable detection levels
Digital data transmission via RS 485 bus and analog 4–20 mA
4 volt-free alarm relay outputs and 1 fault relay
4 analog inputs (4–20 mA), 4 digital inputs, 2 digital outputs
Compatible with detectors from the series: PollyGard 2, PolyXeta 2, PDP-13EX
IP65, operating temperature –5 to +40°C
Plastic housing, dimensions 410 × 285 × 140 mm (L×H×D)
DIRECTIVES:
EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU
EN 50271; EN 61010-1:2010; ANSI/UL 2017 / UL 61010-1; CAN/CSA-C22.2 No. 61010-1
SIL2
Compliance with: EN IEC 61508-1–3; EN 50402; EN 50545-1; EN 378