Fire detection system
Aspirating detection systems
ProPoint PLUS aspirating smoke detectors
ProPoint PLUS aspirating smoke detectors use either ‘optical and CO’ or solely ‘optical’ scattered-light chamber detectors (SCD) and can provide up to four separate detectors within each aspirating unit.Product Description
Power supply: 21–28 VDC
Current consumption: at 24 VDC, 100% Fan, all 4 pipes: 580 mA standby | 620 mA alarm
Temperature range: Tested to EN 54-20: –10°C to 55°C (32°F to 131°F)
Sampled air temperature: –20°C to 60°C
Humidity conditions: 10–93% RH (non-icing / non-condensing), IP30
Detectors per aspirator: 1–4 individual detectors (allowing up to 4 separately identifiable zones)
Optical detection range: 0.12% obs/m to 11% obs/m
CO detection range: 1 to 150 ppm
Optical detection range: 0.02% obs/m to 6.0% obs/m
Hole sensitivity range: 0.5% obs/m to 6.0% obs/m
High-performance optical Scatter Chamber Detectors (SCD) and/or enhanced CO detection
Multilingual, multifunction LCD display
Programmable output contacts: 5 contacts rated 30 VDC 1 A (volt-free switching contacts with 28 programmable options)
Programmable inputs: 3 monitored inputs configurable for isolation, reset, silence, battery fault and mains fault
Event memory / Data storage: 24,000 events stored on a FIFO basis (alarms, actions, faults and data points), approx. 30 days of historical data graphs
Built-in unwanted alarm reduction algorithm
Airflow monitoring per pipe
Dimensions (mm): 380 (H) × 250 (W) × 137 (D)
Standards: EN 54-17, EN 54-20, AS 7240-20, UKCA, CE
ProPoint PLUS optical detection – ‘smoke’ and ‘smoke/CO’
Aspirating detection is a solution suitable for a wide range of fire detection applications. ProPoint PLUS allows the integration of up to four separate detectors within a single aspirator housing, providing four individually identifiable detection zones per device.
Each of the four high-performance Scatter Chamber Detector (SCD) modules can be either optical-only or a combined optical module with enhanced CO sensing, making it particularly suitable for smaller rooms. Independent and integrated alarm decision-making, supported by advanced algorithms, expands the particle detection range, confirms genuine alarms and minimizes unwanted false activations.
Installation, configuration and commissioning of ProPoint PLUS detectors are designed with a strong emphasis on installer convenience. Sensitivity can be adjusted according to Classes A, B or C via the intuitive multilingual LCD display, without the need to connect a computer. Installers can also easily configure detector sensitivity to match the equivalent number of point smoke detectors for each class, ensuring precise tuning for specific application requirements.
Fan speed and airflow configuration allow system performance to be optimized for a wide variety of environments, including both short and long pipe runs.